... | ... | @@ -43,8 +43,8 @@ degree temperature change over 1 minute) was used for the statistics. |
|
|
|
|
|
\- Unused slots were covered to ensure maximum airflow through the
|
|
|
FMCs.
|
|
|
\- PXI Express: National Instruments crates: 3 slots (PXIe-1071) at
|
|
|
ambient temp 25C and 8 slots (PXIe-1062Q) at ambient temp 29C with one
|
|
|
\- PXI Express: National Instruments crates: 4-slot (PXIe-1071) at
|
|
|
ambient temp 25C and 8-slot (PXIe-1062Q) at ambient temp 29C with one
|
|
|
Fine Delay in different slots.
|
|
|
|
|
|
### Data (cards without heatsinks):
|
... | ... | @@ -301,6 +301,16 @@ need to recommend to not use slot 6. |
|
|
</tbody>
|
|
|
</table>
|
|
|
|
|
|
*National Instruments 4-slot PXIe crate PXIe-1071**
|
|
|
| **Fans** | **Slot/FMC** | 2 | 3 | 4 |
|
|
|
| Auto | **Temp** | 57.2 | 55.5 | 55.2 |
|
|
|
| Max | | 48.7 | 47.9 | 46.82 |
|
|
|
|
|
|
*National Instruments 8-slot PXIe crate PXIe-1062Q**
|
|
|
| **Fans** | **Slot/FMC** | 2 | 3 | 4 | 5 | 6 | 7 | 8 |
|
|
|
| Auto | **Temp** | | 76.0 | 74.8 | 77.5 |
|
|
|
| Max | | | 63.3 | 63.5 |(red)64% |
|
|
|
|
|
|
### Data (with heatsinks)
|
|
|
|
|
|
All FMCs were fitted with a [custom CNC-machined
|
... | ... | @@ -454,11 +464,6 @@ Slots 10-15: |
|
|
| **Slot** | 1 | 2 | 3 | 7 | 8 |
|
|
|
| **Temp** | 88.19 | 81.94 | 89.12 | 83.0 | 71.75 |
|
|
|
|
|
|
*National Instruments 3-slot PXIe crate**
|
|
|
| **Fans** | **Slot/FMC** | 2/1 | 2/2 | 3/1 | 3/2 |
|
|
|
| Auto | **Temp** | 57.2 | 55.5 | 55.2 |
|
|
|